Honeywell Gent 13270-04LB

 0

The Honeywell Gent Xenex 13270-04LB is a 4-zone conventional fire alarm control panel, EN54 Parts 2 & 4 certified and LPCB approved. It features an integral power supply, 72-hour battery standby, 2 auxiliary relay contacts, and one-man test and commissioning — ideal for small building fire protection.

The Honeywell Gent Xenex 13270-04LB is a 4-zone conventional fire alarm control panel designed for small building premises requiring cost-effective, reliable fire detection coverage. Certified to EN54 Parts 2 and 4 and LPCB approved, the panel is engineered for simple installation and dependable day-to-day operation, and can be used on installations meeting BS 5839: Part 1. WirelessfirealarmsystemsC-Tec

Each panel contains an integral power supply with battery standby capacity of 72 hours plus 0.5 hours of alarm load (batteries not included — requires 2 x 12V 2.1Ah batteries). The panel drives up to four alarm sounder circuits, includes 2 auxiliary relay contacts, a zone disablement facility, and one-man test and commissioning features, simplifying both installation and ongoing maintenance. It utilizes LPCB approved conventional smoke or heat detectors, deployed on conventional radial wiring layouts using standard 2-core cable. Wirelessfirealarmsystems + 2

The panel includes 1 N/O and 1 N/C auxiliary relay contact pair rated 1A at 24V, and a class change facility operated via a normally open push-button switch located no more than 100m from the panel. Cable entry is provided via 13 top and 13 rear entries, using BS 6387-rated 2-core cable of minimum 1.5mm² CSA. WirelessfirealarmsystemsWirelessfirealarmsystems

Key Features:

  • 4 zones, 4 sounder circuits
  • EN54 Parts 2 & 4 certified, LPCB approved
  • BS 5839: Part 1 compliant
  • Integral power supply with 72-hour battery standby (+ 0.5hr alarm load)
  • 2 auxiliary relay contacts (1 N/O, 1 N/C, 1A at 24V)
  • Zone disablement facility
  • One-man test and commissioning
  • Approx. weight (with batteries): 5.8kg
  • Batteries not included (requires 2 x 12V 2.1Ah)
  • Max sounder circuit load: 0.5A per circuit (total not exceeding 1A)

Ideal Applications:
Small commercial buildings, offices, retail units, and light industrial premises requiring a cost-effective, conventional 4-zone fire alarm control pa